Final | 11/8/2007 | 11/9/2007 | 11/9/2007 | A | PASS |
Bob Reichert
|
|
|
Please call Todd with results - ###-####. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to final, signed structural card
|
Permanent Service | 10/3/2007 | 10/4/2007 | 10/4/2007 | A | PASS |
Bob Reichert
|
|
|
re-inspect, corrections are completed Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corrections made, p/s u/g n ok, 1 meter only
|
Final | 10/3/2007 | 10/3/2007 | 10/3/2007 | P | FAIL |
Bob Reichert
|
|
|
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson met contractor, left correction notice, nec 312.5 all conductors entering enclosure shall have abrasion protection, 250.24 grounding shall be isolated from grounded conductor, renove bonding screw, 110.26(A) shall provide workspace for receptacle, cover shall open, told contractor can't final until they call for permanent service, this 2nd day in a row this was called for final
|
Final | 9/28/2007 | 10/1/2007 | 10/1/2007 | P | CANC |
Bob Reichert
|
|
|
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson called contr, doesn't know why called in, not ready because low voltage under panel and they are planning to re-locate thru irrigation contractor, need to isolate grounded conductor from ground in house panel, provide abrasion protection for all conductors entering enclosure, and provide space to open cover on convenience receptacle, and provide circuit directory
|
Final | 9/28/2007 | 10/1/2007 | 9/28/2007 | A | CANC |
Bob Reichert
|
|
|
THANK YOU!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
|
Electrical Rough-In | 5/4/2007 | 5/4/2007 | 5/4/2007 | A | PASS |
Bob Reichert
|
|
|
this is for an underground inspection Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to cover u/g north and east side bldg along parking lot wall only
|
Electrical Rough-In | 3/26/2007 | 3/26/2007 | 3/26/2007 | P | PART |
Jack Frank
|
|
|
wiring in block wall for lights ok
|
Electrical Rough-In | 12/21/2006 | 12/21/2006 | 12/21/2006 | P | PASS |
Bob Reichert
|
|
|
ali - uffer ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith gec ok to pour
|