Temporary Service | 1/5/2007 | 1/5/2007 | 1/5/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### corr made, t/s o/h n ok
|
Temporary Service | 1/3/2007 | 1/4/2007 | 1/4/2007 | A | FAIL |
Bob Reichert
|
|
|
all american; Phone #: ###-#### note: was told by dj at all american that this used to be a church and that a prop. mgt. co. is going to turn it into apt. - no bld. permit issued -ps- Internet Inspection Request from: Patricia Smith called, left corr notice, nec 312.5 all cndrs shall have abrasion protection entering enclosures,110.12(C) shall provide all screws for panel covers,250.53(G) upper end of electrode shall be flush with or below ground level,230.26 point of attachment of service cndrs shall be min 10' , BCC address shall be posted, job id sticker shall be posted, fee due
|