Final | 4/30/2007 | 5/1/2007 | 5/1/2007 | A | PASS |
Bob Reichert
|
|
|
shawn; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr to survey loose recpts and cover to be flush with recpts, ok to final
|
Final | 4/19/2007 | 4/20/2007 | 4/20/2007 | P | CANC |
William E Thomas
|
|
|
Sean; Phone #: ###-#### Internet Inspection Request from: Stacie Backus contractor is rescheduling this for monday
|
Rough-In Permanent Service | 1/8/2007 | 1/9/2007 | 1/9/2007 | A | PASS |
Jack Frank
|
|
|
SHAWN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles needs to protect cables within 6ft of attic accesses called r/i ok p/s u/g new ok
|
Rough-In Permanent Service | 1/4/2007 | 1/4/2007 | 1/4/2007 | P | FAIL |
Jack Frank
|
|
|
SHAWN ###-#### 300.4(A)(1)&(D) nail plates and 11/4" for high and low voltage cables, 314.43 no nails in plastic boxes, 314.17(C) sheath shall enter box not tape where cables sheath is cut short upstairs in laundry rm switch and basement exit door switch 210.52(B) remove vacuum outlet from S A B C in din. rm334.23 protect all cables 6ft of attic accesses garage and MB closet
|