Permit Information
Permit NumberELE07-00046
StatusFinaled
Name L & K ELECTRIC
Site Address 1680 N WESTLAND DR
Project NameKFC/LJS RESTAURANT
Customer Number 
ePlanReview 
Description
new commerical - complete wiring of building - value is $67,580.00 per initial cert of value ///final value remains the same per faxed document 8-7-07ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/6/20078/6/20078/6/2007PPASS
DetailsJack Frank
Final inspection please. Justin Metcalf will be the contact person. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw
ok
Final4/27/20074/27/20074/27/2007APART
DetailsJack Frank
This inspection is for temporary occupancy only Contact Marvin Phone #: ###-#### Internet Inspection Request from: Laura Longshaw t/o ok card signed
Final4/26/20074/26/20074/26/2007PFAIL
DetailsJack Frank
This inspection will be for a temporary occupancy only. Thank you Phone #: ###-#### Internet Inspection Request from: Laura Longshaw 210.8 com. kit all 15&20 amp 120V recepts shall have gfci protection
Electrical Rough-In4/25/20074/25/20074/25/2007APASS
DetailsJack Frank
Cieling Inspection please. Contact Marvin Miller if there is any problem. Thank you Phone #: ###-#### Internet Inspection Request from: Laura Longshaw
ceilings ok low voltage correction made
Electrical Rough-In4/24/20074/24/20074/24/2007PNR
DetailsJack Frank
Cieling Inspection please. Contact Marvin Miller if there is any problems. Thank you Phone #: ###-#### Internet Inspection Request from: Laura Longshaw
electrical contr ok corrections posted on
BLD06-02189 for low voltage 300.11 830.21&24
Electrical Rough-In4/23/20074/23/20074/23/2007PNR
DetailsJack Frank
Above ceiling inspection please. Thank you
Phone #: ###-#### Internet Inspection Request from: Laura Longshaw
300.11 wires for support of cables , high and low voltage, 400.8 no cords above ceiling time clock above panels
Electrical Rough-In4/19/20074/19/20074/19/2007PPASS
DetailsWilliam E Thomas
This is for a service inspection please. Jason is the contact person. Thank you Phone #: ###-#### Internet Inspection Request from: Laura Longshaw
ri ok
Electrical Rough-In4/18/20074/19/20074/19/2007ANR
DetailsBob Reichert
This will be for a Service Inspection please. Thank you Phone #: ###-#### Internet Inspection Request from: Laura Longshaw gndg not connected, told to call back in
Electrical Rough-In3/14/20073/15/20073/15/2007APASS
DetailsJack Frank
Reinspection for Wall Rough In. ###-#### Marvin Miller. Thank you. Phone #: ###-####
walls ok
Electrical Rough-In3/14/20073/14/20073/14/2007PFAIL
DetailsJack Frank
harven; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles same coorections as before over 360 degrees of bends in conduit, and job not ready
Electrical Rough-In3/12/20073/13/20073/13/2007APART
DetailsJack Frank
This will be for an underground conduit inspection. Please contact Marvin Miller if there is any trouble. Thank you and have a great day. ok
Phone #: ###-####
Electrical Rough-In2/27/20072/27/20072/27/2007PPART
DetailsJack Frank
Underground inspection please. Call Marvin Miller if there is a problem. Thank you for you time. Phone #: ###-#### partial only for front of building to fairview, and from back of building back landscape area still needs inspections for rest of u/g
Electrical Rough-In2/26/20072/27/20072/27/2007ACANC
DetailsPat Lass
Underground inspection please. Noah will be the contact person. Have a great day and thank you Phone #: ###-####
Electrical Rough-In2/27/20072/27/20072/27/2007PCANC
DetailsJack Frank
Underground inspection please. Call Marvin Miller if there is any problems. Thank you Phone #: ###-#### Inspection cancelled from web by: Laura Longshaw
Electrical Rough-In1/29/20071/30/20071/30/2007APASS
DetailsBob Reichert
Reinspection of underground. Please notify Noah with any problems. Thank you. Phone #: ###-#### corr made, ok to cover u/g onlly
Electrical Rough-In1/29/20071/30/20071/29/2007ACANC
DetailsJack Frank
Reinspection of underground. If there are any problems please contact Marvin Miller. Thank you. Phone #: ###-#### Inspection cancelled from web by: Laura Longshaw
Electrical Rough-In1/29/20071/29/20071/29/2007AFAIL
DetailsWilliam E Thomas
This is for a reinspection of the underground. Please contact Marvin Miller if there are any problems. Thank you Phone #: ###-####
1. corrections still not made
Electrical Rough-In1/26/20071/26/20071/26/2007PFAIL
DetailsJack Frank
Reinspection for underground only. If you have any questions please call Marvin Miller. Thank you.
Phone #: ###-#### corrections not made shall not have more than 360 degrees tatal bends in raceway as noted in prior inspection in the AM called note all raceways
Electrical Rough-In1/25/20071/26/20071/26/2007AFAIL
DetailsBob Reichert
This will be for underground only. If you have any questions please call Marv Miller. Thank you. Phone #: ###-#### called left corr notice, nec 352.26 there shall not be over 360 degree bends in raceway
Electrical Rough-In1/17/20071/18/20071/18/2007APART
DetailsJack Frank
This will be for underground on the NE corner only. Contact name Noah Phone #: ###-#### ok
Electrical Rough-In1/4/20071/4/20071/4/2007PPART
DetailsJack Frank
L&K Electric - uffer ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok