Final | 1/29/2007 | 1/29/2007 | 1/29/2007 | P | PASS |
Jack Frank
|
|
|
Jack, the low voltage wiring above the suspended ceiling has been cleaned up. Thanks, Joe Phone #: ###-#### final ok corrections made no card at site
|
Final | 1/25/2007 | 1/25/2007 | 1/25/2007 | P | CANC |
Jack Frank
|
|
|
Final for new bathrooms in back and new data room and breakroom. Suite 195 Phone #: ###-#### electrical contractor permit ok for final, but cannot final till low voltage corrected corr. posted called left message bdl06-03073 830.21-24, 800.21-24 low voltage cales shall be supported and removed from laying on grid ceiling
|
Electrical Rough-In | 1/8/2007 | 1/8/2007 | 1/8/2007 | P | PART |
Jack Frank
|
|
|
Rough in inspection for walls in bathrooms and breakroom and new office Suite 195. South west corner of building facing maple grove. Phone #: ###-#### walls for new office and restrooms ok only
|
Electrical Rough-In | 1/5/2007 | 1/5/2007 | 1/5/2007 | P | FAIL |
William E Thomas
|
|
|
Rough in inspection for wall cover Phone #: ###-#### 1. 314.29 junction boxes shall be accesable
|