Final | 4/20/2007 | 4/20/2007 | 4/20/2007 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/20/2007 at 6:49:05 AM. Contact: ###-####. called contr to tighten 2 recpts, ok to final
|
Electrical Rough-In | 1/9/2007 | 1/9/2007 | 1/9/2007 | P | PASS |
William E Thomas
|
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 1. ri ok
|
Rough-In Permanent Service | 1/5/2007 | 1/8/2007 | 1/8/2007 | A | CANC |
Bob Reichert
|
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see p/s and ri
|
Electrical Rough-In | 1/8/2007 | 1/8/2007 | 1/8/2007 | A | FAIL |
Bob Reichert
|
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member or protected by steel plate,314.20 box shall be flush with finished surface , rear light, 334.30 nm cable shall not be stapled on edge
|
Permanent Service | 1/8/2007 | 1/8/2007 | 1/8/2007 | A | PASS |
Bob Reichert
|
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h n ok
|