Final | 1/31/2007 | 2/1/2007 | 2/1/2007 | A | PASS |
Bob Reichert
|
|
|
The service is ready to be reinspected and the shop is now ready for inspection. Thanks Phone #: ###-#### shop ok to final
|
Permanent Service | 2/1/2007 | 2/1/2007 | 2/1/2007 | A | PASS |
Bob Reichert
|
|
|
The service is ready to be reinspected and the shop is now ready for inspection. Thanks Phone #: ###-#### corr made, p/s o/h rec ok
|
Permanent Service | 1/22/2007 | 1/22/2007 | 1/22/2007 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### corr. called 310.15 (B)(2)(a) table derate conductors, 312.5(C) shall insyall cables as code noted states ,or install conductors in pvc to a Jbox under house then splice to romex, 250.148 splice and grd equip grd in jbox in house (old panel used as jbox), 408.8 panel schedule shall be specific location purpose and use
|
Permanent Service | 1/8/2007 | 1/9/2007 | 1/9/2007 | A | NH |
William E Thomas
|
|
|
Shop note ready to rough yet. Phone #: 208-870-556 1. not home, loud dog in yard
|