Final | 5/17/2007 | 5/17/2007 | 5/17/2007 | P | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Clyde Logan final ok
|
Rough-In Permanent Service | 1/23/2007 | 1/23/2007 | 1/23/2007 | A | PASS |
Pat Lass
|
|
|
Phone #: ###-#### R/I Ok P/S U/g N Ok
|
Rough-In Permanent Service | 1/16/2007 | 1/17/2007 | 1/17/2007 | A | FAIL |
Jack Frank
|
|
|
Electrical rough -in for new residential and permanent service Phone #: ###-#### corr. called 314.16 box fill , 300.4 nail plates and 11/4'' 210.52(A) outlet spacing and 2ft walls, 110.14 bond screws are loose, also using wrong tool for crip sleeves, 250.148 splice all equip grds together 12 and 14 210.11, 210.52(F) all outlets in laundry rm shall be 20 amp, 210.52(B)(1) shall not have switched lighting outlets on S A B C in din rmm outlet outside back not wired, partial corr. only job not ready COW
|