Final | 2/27/2007 | 2/28/2007 | 2/28/2007 | A | PASS |
Jack Frank
|
|
|
###-#### - jeff shell and core ok only survey needs correct panel directory 408.4 shall be specific location purpose and use
|
Final | 2/5/2007 | 2/5/2007 | 2/5/2007 | P | FAIL |
Pat Lass
|
|
|
Please contact Jeff at ###-#### Phone #: ###-#### not attached to proper bld permit
|
Final | 2/1/2007 | 2/1/2007 | 2/1/2007 | P | NR |
Jack Frank
|
|
|
Phone #: ###-#### called contr requested inspection by mistake job not ready
|
Permanent Service | 1/26/2007 | 1/26/2007 | 1/26/2007 | P | PASS |
Jack Frank
|
|
|
re-inspection of grounding Phone #: ###-#### p/s u/g new ok
|
Conference | 1/24/2007 | 1/25/2007 | 1/25/2007 | A | DONE |
Jack Frank
|
|
|
Multiple Grounding Service Phone #: ###-#### ok
|
Permanent Service | 1/21/2007 | 1/22/2007 | 1/22/2007 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### corr. called 250.24(A)(1)terminate all GEC to neutral bus, 250.58 all grd electrodes shall tie togrther to form a common grd electrode system, ID meters
|