Final | 3/13/2007 | 3/14/2007 | 3/14/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### corrections made, ok to final, signed occ card
|
Electrical Rough-In | 3/12/2007 | 3/12/2007 | 3/12/2007 | P | FAIL |
Bob Reichert
|
|
|
Final - if you have questions pls call Mike @ ###-####. Thank! Scheduled by Heather W/ Doherty Phone #: ###-#### called, left messag, left corr notice, nec 408.4 circuit directory shall be clear, concise, and legibly identified, with circuits specific, 110.12(A) ,408.&, unused openings in panels shall be closed, 240.81 circuit breaker handle shall be up for on and down for off, 406.5 recpt faceplates shall completely cover openings, 330.30(B) mc cable shall be strapped within 12" of box, 358.30(A) emt shall be strapped within 3' of box, 422.31(B) shall provide disconnect or lockout for appliances, water heater, 250.104(A) h & c water piping shall be bonded, 110.26 there shall be no foreign piping in work space about equipment, BCC all make-up shall be done-below service panel,all equipment shall be listed by a nationally recognized testing laboratory (furniture), and all covers installed, meter shall be weatherproof
|
Electrical Rough-In | 2/8/2007 | 2/9/2007 | 2/9/2007 | P | PASS |
Bob Reichert
|
|
|
Cover insp. - questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### ric ok
|
Permanent Service | 1/26/2007 | 1/26/2007 | 1/26/2007 | P | PASS |
Bob Reichert
|
|
|
For questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### p/s u/g rec ok
|
Permanent Service | 1/23/2007 | 1/25/2007 | 1/25/2007 | P | FAIL |
Bob Reichert
|
|
|
replacing bad panel - need insp. to have Idaho Power to turn power back on. For questions pls call Ryan w/doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### met contr, job not ready, talked about criteria for bringing service up to code, inside panel not mounted, nm cable from old panel not installed
|
Electrical Rough-In | 1/17/2007 | 1/17/2007 | 1/17/2007 | P | PASS |
Bob Reichert
|
|
|
floor insp. for questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### ok to cover u/g from wall to floor box
|