Final | 3/23/2007 | 3/26/2007 | 3/26/2007 | A | PASS |
William E Thomas
|
|
|
please contact Patrick, thank you Phone #: ###-#### final ok
|
Final | 3/20/2007 | 3/20/2007 | 3/20/2007 | P | FAIL |
Bob Reichert
|
|
|
ready for final, please contact Patrick, thank you Phone #: ###-#### called contr, left corr notice, nec 352.30(A) rnc shall be strapped within 3' of termination, 408.4 & 110.22 circuit directory shall be clear concise and specific to its purpose, 110.26(A) work space shall be provided about inside and outside panels as code states, BCC job shall be completed with all devices installed- rear outlet
|
Electrical Rough-In | 3/20/2007 | 3/20/2007 | 3/20/2007 | P | CANC |
Bob Reichert
|
|
|
Please contact Miles, thank you Phone #: ###-#### Inspection cancelled from web by: Wendy Waters
|
Permanent Service | 1/25/2007 | 1/25/2007 | 1/25/2007 | P | PART |
Pat Lass
|
|
|
Pat HOME OWNER WITH POWER; Phone #: ###-#### Internet Inspection Request from: Darla Downs P/S U/G R Ok for power will call for final tomorrow just to look at outside.
|
Electrical Rough-In | 1/19/2007 | 1/19/2007 | 1/19/2007 | P | PASS |
Bob Reichert
|
|
|
Please contact Patrick, thank you Phone #: ###-#### ric ok
|
Electrical Rough-In | 1/18/2007 | 1/18/2007 | 1/18/2007 | P | NR |
Bob Reichert
|
|
|
Ready for rough-in, Please contact Pat, thank you Phone #: ###-#### told to call when ready, still wiring boxes and lights
|