Final | 4/2/2007 | 4/2/2007 | 4/2/2007 | P | PASS |
Bob Reichert
|
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corrections made, ok to cover u/g, called contr to ensure backfill not big rocks, but sand, close ko's, ok to final
|
Final | 3/23/2007 | 3/26/2007 | 3/26/2007 | A | FAIL |
William E Thomas
|
|
|
Wayne Trench ; Phone #: ###-#### Internet Inspection Request from: Stacie Backus 310.7 conductors shall be identified for direct burial. 110.3B manufacturers instructions-- trailer shall be fed with four wires to the panel
|
Final | 1/30/2007 | 1/30/2007 | 1/30/2007 | P | FAIL |
William E Thomas
|
|
|
WAYNE; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 1. 400.5A - sow cord is rated at 70A max. 2. trailer label states power is to be 100A.
|
Permanent Service | 1/26/2007 | 1/29/2007 | 1/29/2007 | A | CANC |
William E Thomas
|
|
|
Wayne ###-####
|
Rough-In Permanent Service | 1/29/2007 | 1/29/2007 | 1/29/2007 | P | PASS |
William E Thomas
|
|
|
Wayne ###-#### 1. p/s o/h n ok 2. trailer needs to be hooked up per manufacturer name plate specs.
|