Final | 3/20/2007 | 3/20/2007 | 3/20/2007 | P | PASS |
Bob Reichert
|
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final, signed occ card
|
Permanent Service | 3/6/2007 | 3/7/2007 | 3/7/2007 | A | PASS |
Bob Reichert
|
|
|
Paul; Phone #: ###-#### Internet Inspection Request from: Stacie Backus p/s u/g n ok
|
Electrical Rough-In | 2/16/2007 | 2/16/2007 | 2/16/2007 | P | PASS |
Bob Reichert
|
|
|
ok to cover u/g, corr made
|
Electrical Rough-In | 2/16/2007 | 2/16/2007 | 2/16/2007 | P | FAIL |
Bob Reichert
|
|
|
paul - underground ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, left corr notice, nec 344.26 & 352.26 there shall not be more than the equivalent of 4 quarter bends (360 degree total) between pull points, BCC all make-up shall be done- complete raceway sys before cover
|
Electrical Rough-In | 2/13/2007 | 2/14/2007 | 2/14/2007 | A | PART |
Mike Kinnear
|
|
|
PAUL - UNDERGROUNG AND UFER; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok cover keyoffs & ufer ground
|