Final | 12/18/2007 | 12/19/2007 | 12/19/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: David Seilheimer corrections made, ok to final
|
Final | 12/15/2007 | 12/17/2007 | 12/17/2007 | A | FAIL |
Jack Frank
|
|
|
Front Door Open, other trades may be on site. Owners (Mark & Debra) live next door @ 1812 Lemp. Phone #: ###-#### Internet Inspection Request from: David Seilheimer corr fee due called left message 210.52(A) needs outlets for wall space back bed rm upstairs right of closet, downstairs south bed rm left of closet, 200.11 reversed polarity south upstairs bed rm left of front window, 406.4(A B D) recepts loose and set back in plates, 408.4 be specific purpose and use
|
Electrical Rough-In | 8/2/2007 | 8/3/2007 | 8/3/2007 | P | PASS |
Pat Lass
|
|
|
Dave, supervising journeyman on site. Phone #: ###-#### Internet Inspection Request from: David Seilheimer
|
Conference | 2/8/2007 | 2/9/2007 | 2/9/2007 | P | PART |
Pat Lass
|
|
|
Meet with Dave at your convienance Phone #: ###-#### service ok
|
Permanent Service | 2/9/2007 | 2/9/2007 | 2/9/2007 | P | PART |
Pat Lass
|
|
|
Meet with Dave at your convienance Phone #: ###-#### P/S O/H R Ok
|