DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/8/20078/8/20078/8/2007PPASS
DetailsBob Reichert
hz Phone #: ###-#### ok to final
Electrical Rough-In4/25/20074/25/20074/25/2007PPASS
DetailsBob Reichert
H Z garage; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover u/g to garage and ric ok
Electrical Rough-In2/20/20072/20/20072/20/2007PPASS
DetailsBob Reichert
hz; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ric ok
Permanent Service2/20/20072/20/20072/20/2007PPASS
DetailsBob Reichert
hz; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h rec ok
Rough-In Permanent Service2/14/20072/15/20072/15/2007AFAIL
DetailsBob Reichert
hz ###-#### called, left corr notice,n BCC address shall be posted, NEC 300.5 u/g shall be 18" deep, 334.30 guy kit shall be installed at service, 210.52(A)(1) recpts shall be installed such that no point is over 6' from outlet, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member