Final | 8/8/2007 | 8/8/2007 | 8/8/2007 | P | PASS |
Bob Reichert
|
|
|
hz Phone #: ###-#### ok to final
|
Electrical Rough-In | 4/25/2007 | 4/25/2007 | 4/25/2007 | P | PASS |
Bob Reichert
|
|
|
H Z garage; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover u/g to garage and ric ok
|
Electrical Rough-In | 2/20/2007 | 2/20/2007 | 2/20/2007 | P | PASS |
Bob Reichert
|
|
|
hz; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ric ok
|
Permanent Service | 2/20/2007 | 2/20/2007 | 2/20/2007 | P | PASS |
Bob Reichert
|
|
|
hz; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h rec ok
|
Rough-In Permanent Service | 2/14/2007 | 2/15/2007 | 2/15/2007 | A | FAIL |
Bob Reichert
|
|
|
hz ###-#### called, left corr notice,n BCC address shall be posted, NEC 300.5 u/g shall be 18" deep, 334.30 guy kit shall be installed at service, 210.52(A)(1) recpts shall be installed such that no point is over 6' from outlet, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member
|