Final | 7/11/2007 | 7/12/2007 | 7/12/2007 | A | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 7/11/2007 at 12:40:43 PM. Contact: ###-####. final ok
|
Rough-In Permanent Service | 2/19/2007 | 2/20/2007 | 2/20/2007 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 2/19/2007 at 1:24:04 PM. Contact: ###-####. ok cover ri corrections made p/s u/g n ok
|
Rough-In Permanent Service | 2/16/2007 | 2/16/2007 | 2/16/2007 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/16/2007 at 8:14:08 AM. Contact: ###-####. called, left corr notice, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members,210.70(A)(2)(b) lighting outlets shall be installed at outdoor entrances, 210.8(A) bath shall have recpt installed, BCC make-up shall be done
|
Electrical Rough-In | 2/14/2007 | 2/15/2007 | 2/15/2007 | A | FAIL |
Bob Reichert
|
|
|
zane; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, BCC address shall be posted, job id sticker shall be posted, approved set of plans shall be on job
|