Final | 6/27/2007 | 6/27/2007 | 6/27/2007 | P | PASS |
Jack Frank
|
|
|
JADE Phone #: ###-#### ok
|
Electrical Rough-In | 4/10/2007 | 4/10/2007 | 4/10/2007 | P | PASS |
Jack Frank
|
|
|
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
|
Rough-In Permanent Service | 4/2/2007 | 4/2/2007 | 4/2/2007 | P | FAIL |
Jack Frank
|
|
|
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. fee due called left message, all violations not made and new ones created, 300.14 6" free conductor, 300.4(D) 11/4" cables parallel to studs, 300.15 boxes required all locations outside fixtures,110.3(A) replace broken box kit., 210.52(B) remove range hood, back entry recept and anything eles not allowed on SABC, 314.43 no screws or nails allowed in plastic boxes
|
Permanent Service | 4/2/2007 | 4/2/2007 | 4/2/2007 | P | PASS |
Jack Frank
|
|
|
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h rec. ok
|
Permanent Service | 3/26/2007 | 3/26/2007 | 3/26/2007 | P | CANC |
Jack Frank
|
|
|
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see added r/i p/s
|
Rough-In Permanent Service | 3/26/2007 | 3/26/2007 | 3/26/2007 | P | FAIL |
Jack Frank
|
|
|
corr met contr, 300.4 nail plates and 11/4" 314.16 box fill, 334.30,314.17(C) staple romex 8"of boxes, 110.3(A) repair,replace damaged romex wall by back batjrm, 250.66T #4 to u/g water pipe, 250.24(A)(5) isolate grds neuts at subpanels,, 250.148 splice all equip grds at boxes, 300.15 shall install boxes at all outlets switch recepts, fixtures, BCC complete all makeup
|
Permanent Service | 3/13/2007 | 3/13/2007 | 3/13/2007 | P | FAIL |
Jack Frank
|
|
|
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called left message still needs bld permit for job before electrical inspection is requested told contractor that the first time I came out
|
Permanent Service | 2/20/2007 | 2/20/2007 | 2/20/2007 | P | FAIL |
Jack Frank
|
|
|
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called needs bld permit for changing single residence too duplex called left message
|