Final | 3/3/2008 | 3/3/2008 | 3/3/2008 | P | PASS |
Pat Lass
|
|
|
eric Phone #: ###-####
|
Final | 12/28/2007 | 12/28/2007 | 12/28/2007 | P | FAIL |
Bob Reichert
|
|
|
eric Phone #: ###-#### met owner, left correction notice, nec 210.12(B) bedrooms shall have afci protection installed, 406.8(A) garage outdoor recptacle shall have in-use cover installed, asked owner to strap conduit that was existing in garage, everything else in house inspected, told could move in, but we have to inspect afci and owner must provide room for access
|
Conference | 12/27/2007 | 12/27/2007 | 12/28/2007 | P | DONE |
Bob Reichert
|
|
|
eric Phone #: ###-#### met owner , talked about in-use covers, strapping risers, bond screw, outside gfci, kitchen gfci, dead receptacles, open neutrals, open grounds, closet lights, abandon wire not used, flush switch plates, heater disconnect,flex over nm cable, staple nm cable at heater area, finish install lights, switches, dead receptacles, afci for bedrooms, if move in, allow 3' clear space around walls for inspection, owner made list of items
|
Final | 12/26/2007 | 12/27/2007 | 12/27/2007 | P | CANC |
Bob Reichert
|
|
|
eric Phone #: ###-#### see conference
|
Electrical Rough-In | 9/20/2007 | 9/20/2007 | 9/20/2007 | P | PASS |
Pat Lass
|
|
|
eric Phone #: ###-####
|
Electrical Rough-In | 9/17/2007 | 9/17/2007 | 9/17/2007 | P | NR |
Pat Lass
|
|
|
eric Note: cover up Phone #: ###-#### had conf with homeowner. many violations existed no make up was done
|
Electrical Rough-In | 7/10/2007 | 7/10/2007 | 7/10/2007 | P | PART |
Pat Lass
|
|
|
eric - cover; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang under floor ok
|
Electrical Rough-In | 7/9/2007 | 7/9/2007 | 7/9/2007 | P | NR |
Pat Lass
|
|
|
eric Phone #: ###-#### junction box shall not be burried
|
Electrical Rough-In | 4/2/2007 | 4/3/2007 | 4/3/2007 | P | CANC |
William E Thomas
|
|
|
eric Please call first before going out; Phone #: ###-#### Internet Inspection Request from: Darla Downs wrong type inspection
|
Conference | 4/3/2007 | 4/3/2007 | 4/3/2007 | P | DONE |
William E Thomas
|
|
|
eric Please call first before going out; Phone #: ###-#### Internet Inspection Request from: Darla Downs answered questions about his basement and what was required as far as spacing between outlets.
|
Permanent Service | 4/3/2007 | 4/3/2007 | 4/3/2007 | P | PASS |
William E Thomas
|
|
|
eric Please call first before going out; Phone #: ###-#### Internet Inspection Request from: Darla Downs p/s o/h reconnect ok
|
Conference | 2/23/2007 | 2/23/2007 | 2/23/2007 | P | CANC |
Pat Lass
|
|
|
Eric, after 2:30 today please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt had conf about total rewire
|
Conference | 2/20/2007 | 2/20/2007 | 2/20/2007 | P | CANC |
Pat Lass
|
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|