Final | 3/1/2007 | 3/1/2007 | 3/1/2007 | P | PASS |
William E Thomas
|
|
|
FINAL OK
|
Permanent Service | 3/1/2007 | 3/1/2007 | 3/1/2007 | P | PASS |
William E Thomas
|
|
|
P/S O/H RECONNECT OK
|
Permanent Service | 3/1/2007 | 3/1/2007 | 3/1/2007 | P | CANC |
William E Thomas
|
|
|
Work performed by Aaron White. Phone #: ###-####
|
Permanent Service | 2/26/2007 | 2/26/2007 | 2/26/2007 | P | FAIL |
Jack Frank
|
|
|
Call Gary ###-#### ofr access. Work performed by Joe Schneehagen. Phone #: ###-#### fee due corr. called 110.3(B) use manufactures breakers only, 110.12(A),and 408.7 seal all unused openings KOs and breaker, 300.10&12 install locknuts on all fittings and tighten all locknuts nipple between meter and paanel and fitting in back of panel, 250.64(E) use plastic or listed fitting for GEC, 40804 needs panel directory
|
Permanent Service | 2/23/2007 | 2/26/2007 | 2/26/2007 | A | NH |
Jack Frank
|
|
|
Work performed by Aaron White. Phone #: ###-#### called left message notice posted , wrong address?
|