Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE07-00648
StatusFinaled
Name SZURGOT ELECTRIC
Site Address 2799 E HARD ROCK DR
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Wire new home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Conference6/6/20076/7/20076/7/2007ADONE
DetailsWilliam E Thomas
Conference with builder, electrician and inspector for island outlets. Please call to let us know what time. Thanks Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
Final6/7/20076/7/20076/7/2007PPASS
DetailsWilliam E Thomas
Conference with builder, electrician and inspector for island outlets. Please call to let us know what time. Thanks Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
final ok--per survey note-210.52 counter recep locations
Final5/9/20075/9/20075/9/2007PFAIL
DetailsJack Frank
This is a parade home, so there is furniture in it. Please call Mike at ###-#### before you head to inspection, so he can move anything you need. The builder has sold this home, but at least needs temporary occupancy if possible, for the loan. Thanks Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
corr fee due called 210.52(A) outlet spacing MB by fixed panel of back door, 210.52(C)(5) exception(2) also300.14, 210.52(C)(1) ,and 314.16&17 no outlets below countertop unless flat across entire surface, box fill required outlet spacing, short wires, sheath not in box cutin box clamps broken out, 408.4 circuit dirctories shall be secific,410.4 heat lamp install in shower stall subject to getting wet,680.73&110.3(B) access for jtub
Final5/8/20075/9/20075/9/2007PCANC
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot Inspection cancelled from web by: Barbara Szurgot
Rough-In Permanent Service3/8/20073/8/20073/8/2007PPASS
DetailsMike Kinnear
Phone #: ###-#### ok cover ri note need to have low/high voltage switghing data at final inspection p/s u/g n ok