Final | 4/12/2007 | 4/12/2007 | 4/12/2007 | P | PASS |
Pat Lass
|
|
|
Phone #: ###-####
|
Rough-In Permanent Service | 3/6/2007 | 3/6/2007 | 3/6/2007 | P | PASS |
William E Thomas
|
|
|
reinspection Phone #: ###-#### ri ok p/s o/h n ok
|
Rough-In Permanent Service | 3/1/2007 | 3/1/2007 | 3/1/2007 | P | PART |
Pat Lass
|
|
|
Phone #: ###-#### r/I Ok service failed mast too small isolated raceway not grounded no main bonding jumper and GEC not to neutral improper iuse of fittings.
|