Final | 4/15/2008 | 4/15/2008 | 4/15/2008 | P | PASS |
Jack Frank
|
|
|
david Phone #: ###-#### ok needs inuse cover back recept
|
Electrical Rough-In | 12/26/2007 | 12/26/2007 | 12/26/2007 | P | PASS |
Bob Reichert
|
|
|
david Phone #: ###-#### corrections made, met owner, ric ok
|
Electrical Rough-In | 12/12/2007 | 12/12/2007 | 12/12/2007 | P | FAIL |
Bob Reichert
|
|
|
david Phone #: ###-#### met owner, left correction notice, BCC all make-up shall be done,NEC 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be stapled within 8" of box, 314.20 box shall be flush with finished surface of combustible material, 250.148(C) shall ground metal box
|
Conference | 11/1/2007 | 11/2/2007 | 11/2/2007 | A | DONE |
Bob Reichert
|
|
|
david Phone #: ###-#### reviewed circuits, afci for bedroom, 1 1/4" for holes and nm cable, make-up and when to call for ri inspection
|