DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/15/20084/15/20084/15/2008PPASS
DetailsJack Frank
david Phone #: ###-#### ok needs inuse cover back recept
Electrical Rough-In12/26/200712/26/200712/26/2007PPASS
DetailsBob Reichert
david Phone #: ###-#### corrections made, met owner, ric ok
Electrical Rough-In12/12/200712/12/200712/12/2007PFAIL
DetailsBob Reichert
david Phone #: ###-#### met owner, left correction notice, BCC all make-up shall be done,NEC 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be stapled within 8" of box, 314.20 box shall be flush with finished surface of combustible material, 250.148(C) shall ground metal box
Conference11/1/200711/2/200711/2/2007ADONE
DetailsBob Reichert
david Phone #: ###-#### reviewed circuits, afci for bedroom, 1 1/4" for holes and nm cable, make-up and when to call for ri inspection