Final | 1/4/2011 | 1/4/2011 | 1/4/2011 | P | PASS |
Bob Reichert
|
|
|
Dina please call before going out Phone #: ###-#### moved in, could not check all receptacles, ok final
|
ELE-Aging Inspection | 12/22/2009 | 12/22/2009 | 12/23/2009 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 12/23/2009 | 12/23/2009 | 12/23/2009 | A | PASS |
Jack Frank
|
|
|
no action
|
Electrical Rough-In | 3/27/2008 | 3/28/2008 | 3/28/2008 | A | PASS |
Bob Reichert
|
|
|
dena - re-inspection Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 2/22/2008 | 2/22/2008 | 2/22/2008 | P | FAIL |
Bob Reichert
|
|
|
dina Phone #: ###-#### corrections not made, created more violations trying to make corrections, called owner and said that we are supposed to pull permit after two inspections and have them get a licensed electrical contractor to do the work. They are talking it over.
|
Electrical Rough-In | 1/22/2008 | 1/23/2008 | 1/23/2008 | P | FAIL |
Bob Reichert
|
|
|
dina Note: able to cover Phone #: ###-#### met owner, left correction notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) receptacles shall be spaced such that no point along floor line is more than 6' from an outlet, 300.14 at least 6" of free conductor length shall be left in box for splicing, BCC all make-up shall be done, shall add smoke detectors as required
|
Conference | 3/8/2007 | 3/9/2007 | 3/9/2007 | A | DONE |
Bob Reichert
|
|
|
dina; Phone #: ###-#### Internet Inspection Request from: Darla Downs reviewed requirements for recpts, lights, how to call for inspection, owner to do the work, not others
|