Final | 7/17/2007 | 7/17/2007 | 7/17/2007 | P | PASS |
Bob Reichert
|
|
|
duane ; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corr made, ok to final
|
Final | 7/16/2007 | 7/16/2007 | 7/16/2007 | P | FAIL |
Bob Reichert
|
|
|
DUANE Phone #: ###-#### called, left corr notice, BCC all work shall be completed-plates on switches and recpts, disposal wired, nec 404.9 and 406.5 switch and recpt plates shall seat against mounting surface, 440.4 overcurrent device for a/c shall not exceed mfgrs nameplate rating, 110.3(B) shall install devices per instructions with listing- no reverse polarity
|
Final | 7/13/2007 | 7/16/2007 | 7/16/2007 | A | CANC |
Jack Frank
|
|
|
duane Phone #: ###-#### no power , power down
|
Electrical Rough-In | 4/4/2007 | 4/5/2007 | 4/5/2007 | A | CANC |
Bob Reichert
|
|
|
duane Note: new box power line; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong type inspection, see p/s
|
Permanent Service | 4/5/2007 | 4/5/2007 | 4/5/2007 | A | PASS |
Bob Reichert
|
|
|
duane Note: new box power line; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g rec ok
|
Electrical Rough-In | 3/21/2007 | 3/22/2007 | 3/22/2007 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/21/2007 at 12:41:31 PM. Contact: ###-####. ric ok lower level
|
Conference | 3/8/2007 | 3/9/2007 | 3/9/2007 | A | DONE |
Jack Frank
|
|
|
###-#### duane added r/i for fam. rm. conference ok owner needs to update permit for rm count and 400 amp service
|
Electrical Rough-In | 3/9/2007 | 3/9/2007 | 3/9/2007 | A | PART |
Jack Frank
|
|
|
###-#### duane new fam rm ok only
|