Conference | 9/25/2007 | 9/26/2007 | 9/26/2007 | A | DONE |
Bob Reichert
|
|
|
jesse - please call 1/2 hr prior to inspection Phone #: ###-#### looked at switchgear room to see about door, it will be ok to put door on, signed occupancy card and amended 9-25-07 inspection notes
|
Final | 9/26/2007 | 9/26/2007 | 9/26/2007 | A | PASS |
Bob Reichert
|
|
|
jesse - please call 1/2 hr prior to inspection Phone #: ###-#### ok to final
|
Final | 9/25/2007 | 9/25/2007 | 9/26/2007 | P | PASS |
Bob Reichert
|
|
|
jessie Note: please call 15 min prior to inspection Phone #: ###-#### corrections made, ok to final, signed occupancy card
|
Final | 8/22/2007 | 8/23/2007 | 8/23/2007 | A | PART |
Bob Reichert
|
|
|
jessie Phone #: ###-#### met elect, left corr notice, nec 605.7 multiwire branch ckts to partitions shall be provided with a means to simultaneously disconnect all ungrounded conductors at the panelboard where the ckt originates, signed t/o card
|
Electrical Rough-In | 8/20/2007 | 8/20/2007 | 8/20/2007 | P | CANC |
Bob Reichert
|
|
|
ceiling; hallways; Jesse; Phone #: ###-#### Internet Inspection Request from: Hattie James contractor called in wrong building
|
Electrical Rough-In | 8/1/2007 | 8/2/2007 | 8/2/2007 | A | PASS |
Mike Kinnear
|
|
|
jessie - 2nd floor hallway and elevator lobby Phone #: ###-#### ok cover ceiling only
|
Permanent Service | 5/18/2007 | 5/21/2007 | 5/21/2007 | A | PASS |
Bob Reichert
|
|
|
jessie; Phone #: ###-#### Internet Inspection Request from: Victoria Beall told to be sure labels installed, ok to energize 2nd floor dist panel from main gear in basement, no meters rq'd
|
Electrical Rough-In | 5/16/2007 | 5/16/2007 | 5/16/2007 | P | PASS |
Bob Reichert
|
|
|
2nd floor ceiling ok to cover except halls
|
Permanent Service | 5/16/2007 | 5/16/2007 | 5/16/2007 | P | CANC |
Bob Reichert
|
|
|
Jesse; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt wrong type inspection, see ri
|
Rough-In Permanent Service | 5/14/2007 | 5/15/2007 | 5/15/2007 | A | FAIL |
Bob Reichert
|
|
|
jessie - ceiling ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith met elect, told corr necessary are nec 330.30(B) mc cable shall be supported within 12" of terminations, 110.26(F)(1) drip protection for for foreign piping over panels,
|
Electrical Rough-In | 4/18/2007 | 4/19/2007 | 4/19/2007 | A | PASS |
Bob Reichert
|
|
|
For Basement; Phone #: ###-#### Jessie Internet Inspection Request from: Stacie Backus ok to cover basement storage area west side
|
Electrical Rough-In | 3/20/2007 | 3/21/2007 | 3/21/2007 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 3/20/2007 at 1:34:35 PM. Contact: ###-####. ok cover ext walls only
|
Electrical Rough-In | 3/8/2007 | 3/9/2007 | 3/9/2007 | A | PART |
Jack Frank
|
|
|
david; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 2nd floor interior walls ok
|