Permit Information
Permit NumberELE07-00794
StatusFinaled
Name ELECTRIC SERVICE & CONTRACT CO
Site Address 3501 W ELDER ST
Project NameUNA MAS BLDG-2ND FLR
Customer Number2702
ePlanReview 
Description
TI new lighting, panel boards, branch circuit, etc. // initial value $120,552 ///final value is $149,291 per faxed document 10-18-07ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Conference9/25/20079/26/20079/26/2007ADONE
DetailsBob Reichert
jesse - please call 1/2 hr prior to inspection Phone #: ###-#### looked at switchgear room to see about door, it will be ok to put door on, signed occupancy card and amended 9-25-07 inspection notes
Final9/26/20079/26/20079/26/2007APASS
DetailsBob Reichert
jesse - please call 1/2 hr prior to inspection Phone #: ###-#### ok to final
Final9/25/20079/25/20079/26/2007PPASS
DetailsBob Reichert
jessie Note: please call 15 min prior to inspection Phone #: ###-#### corrections made, ok to final, signed occupancy card
Final8/22/20078/23/20078/23/2007APART
DetailsBob Reichert
jessie Phone #: ###-#### met elect, left corr notice, nec 605.7 multiwire branch ckts to partitions shall be provided with a means to simultaneously disconnect all ungrounded conductors at the panelboard where the ckt originates, signed t/o card
Electrical Rough-In8/20/20078/20/20078/20/2007PCANC
DetailsBob Reichert
ceiling; hallways; Jesse; Phone #: ###-#### Internet Inspection Request from: Hattie James contractor called in wrong building
Electrical Rough-In8/1/20078/2/20078/2/2007APASS
DetailsMike Kinnear
jessie - 2nd floor hallway and elevator lobby Phone #: ###-#### ok cover ceiling only
Permanent Service5/18/20075/21/20075/21/2007APASS
DetailsBob Reichert
jessie; Phone #: ###-#### Internet Inspection Request from: Victoria Beall told to be sure labels installed, ok to energize 2nd floor dist panel from main gear in basement, no meters rq'd
Electrical Rough-In5/16/20075/16/20075/16/2007PPASS
DetailsBob Reichert
2nd floor ceiling ok to cover except halls
Permanent Service5/16/20075/16/20075/16/2007PCANC
DetailsBob Reichert
Jesse; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt wrong type inspection, see ri
Rough-In Permanent Service5/14/20075/15/20075/15/2007AFAIL
DetailsBob Reichert
jessie - ceiling ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith met elect, told corr necessary are nec 330.30(B) mc cable shall be supported within 12" of terminations, 110.26(F)(1) drip protection for for foreign piping over panels,
Electrical Rough-In4/18/20074/19/20074/19/2007APASS
DetailsBob Reichert
For Basement; Phone #: ###-#### Jessie Internet Inspection Request from: Stacie Backus ok to cover basement storage area west side
Electrical Rough-In3/20/20073/21/20073/21/2007APASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 3/20/2007 at 1:34:35 PM. Contact: ###-####. ok cover ext walls only
Electrical Rough-In3/8/20073/9/20073/9/2007APART
DetailsJack Frank
david; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
2nd floor interior walls ok