Permit Information
Permit NumberELE07-00815
StatusExpired
Name PRECISION PUMPING SYSTEMS
Site Address 512 S MICHAEL ST
Project Name 
Customer Number 
ePlanReview 
Description
Remodel and wiring. Initial value $3000 per cert.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Rough-In Permanent Service5/8/20075/9/20075/9/2007ACANC
DetailsBob Reichert
robert - upstairs; Phone #: ###-#### Internet Inspection Request from: Victoria Beall wrong type request, see ri
Electrical Rough-In5/9/20075/9/20075/9/2007APASS
DetailsBob Reichert
robert - upstairs; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ric ok main level only
Electrical Rough-In4/2/20074/3/20074/3/2007PPASS
DetailsBob Reichert
jim - pls call 30 min prior to inspect; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corrections made, ric basement only ok
Electrical Rough-In3/28/20073/28/20073/28/2007PFAIL
DetailsBob Reichert
Jim pls call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Stacie Backus left corr notice,nec 300.14 at least 6" free conductor shall be left from where conductor enters box for splicing, told to call when fixed, downstairs area only for this part
Electrical Rough-In3/22/20073/22/20073/22/2007PNR
DetailsBob Reichert
jim - pls call 45 prior to inspect; Phone #: ###-#### Internet Inspection Request from: Victoria Beall told needed standoffs for edgewise type const, explained 1 1/4"
Electrical Rough-In3/14/20073/14/20073/14/2007PNR
DetailsMike Kinnear
Jim pls call 45 minutes prior for access.; Phone #: ###-#### Internet Inspection Request from: Stacie Backus t/w owner he needs to get bld permit & then call for inspections