Temporary Service | 3/20/2007 | 3/21/2007 | 3/21/2007 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/20/2007 at 3:40:45 PM. Contact: ###-####. corrections made, t/s u/g n ok
|
Temporary Service | 3/20/2007 | 3/20/2007 | 3/20/2007 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/20/2007 at 10:28:37 AM. Contact: ###-####. called contr, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken parts-50a recpt, there shall be no contamination-inside panel, there shall be no damaged parts-gec, BCC job id sticker shall be posted
|