Final | 8/13/2007 | 8/13/2007 | 8/13/2007 | P | PASS |
Jack Frank
|
|
|
jason Phone #: ###-#### ok corrections made
|
Final | 7/6/2007 | 7/9/2007 | 7/9/2007 | A | FAIL |
Jack Frank
|
|
|
jason - swimming pool; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corr. called 110.26(F)(2) needs clearence for panel fence and hydraulic lines in the way, 250.199 shall not ID #6 or smaller equip grd, 680.24 shall provide listed pool light box for pool fixture shall not terminate cord into panel for pool equipment
|
Electrical Rough-In | 4/9/2007 | 4/10/2007 | 4/10/2007 | P | PASS |
William E Thomas
|
|
|
Jason Pool equal potential ground; Phone #: ###-#### Internet Inspection Request from: Stacie Backus bonding ok for grid
|
Electrical Rough-In | 3/19/2007 | 3/20/2007 | 3/20/2007 | A | PASS |
William E Thomas
|
|
|
jason - bonding; Phone #: ###-#### Internet Inspection Request from: Victoria Beall shell bonding ok
|