Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE07-00935
StatusFinaled
Name RELIABLE ELECTRIC INC
Site Address 614 N 5TH ST
Project Name 
Customer Number 
ePlanReview 
Description
this is multi-family with 6 apartments in 1 unit
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/18/20081/22/20081/22/2008APASS
DetailsPat Lass
MIke Phone #: ###-####
final ok with a survey for gfci within 6 ft of a sink and lock-outs for heaters
Permanent Service10/11/200710/12/200710/12/2007APASS
DetailsPat Lass
Mike ###-#### ///please call 15min - 1 hr prior to meet
P/S O/H R Ok
Permanent Service9/7/20079/7/20079/7/2007PFAIL
DetailsWilliam E Thomas
Mike ###-####
. 1. meyers hubs not rated for line side grounding. .
Permanent Service9/7/20079/7/20079/7/2007PFAIL
DetailsWilliam E Thomas
Mike ###-####
. 1. meyers hubs do not have right grounding locknuts for line-side use. .
Electrical Rough-In7/20/20077/20/20077/20/2007PPASS
DetailsWilliam E Thomas
r/i for 2nd floor-- mike-- ###-#### -
1. walls and ceiling only-- ri ok
Electrical Rough-In7/5/20077/6/20077/6/2007PCANC
DetailsJim Schmer
mike-- ###-#### -1st floor -call 1st before insp 1 hr if possible
Conference3/21/20073/22/20073/22/2007APART
DetailsPat Lass
mike ###-####--call 1st before insp
talked about new service and if romex is permitted for a six unit dwelling