Final | 5/2/2007 | 5/2/2007 | 5/2/2007 | P | PASS |
Mike Kinnear
|
|
|
ok final signed card
|
Final | 4/30/2007 | 4/30/2007 | 4/30/2007 | P | NR |
Mike Kinnear
|
|
|
Carl; Phone #: ###-#### Internet Inspection Request from: Andrea Whiteman not ready no x-ray mech installed & no listing for for cabinet pedistalls
|
Electrical Rough-In | 4/23/2007 | 4/25/2007 | 4/25/2007 | A | PASS |
Mike Kinnear
|
|
|
carl Note: ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok cover ceiling only
|
Permanent Service | 4/20/2007 | 4/20/2007 | 4/20/2007 | P | PASS |
Mike Kinnear
|
|
|
carl; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s u/g n ok note just needs meter
|
Electrical Rough-In | 3/27/2007 | 3/27/2007 | 3/27/2007 | P | PASS |
Mike Kinnear
|
|
|
carl; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok cover walls & under slab conduit
|
Electrical Rough-In | 3/26/2007 | 3/27/2007 | 3/27/2007 | A | FAIL |
Mike Kinnear
|
|
|
Carl; Phone #: ###-#### Internet Inspection Request from: Stacie Backus nec 300.4(D) straping 1 1/4 inch from framing member
|
Electrical Rough-In | 3/22/2007 | 3/26/2007 | 3/26/2007 | A | FAIL |
William E Thomas
|
|
|
Need wall cover & concrete floor inspection. Contact Karl Paige. Phone #: ###-#### 358.30 & 330.30 emt/mc not fastened securley in place at boxes within the given parameters of each material.
|