Temporary Service | 4/2/2007 | 4/3/2007 | 4/3/2007 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 4/2/2007 at 3:24:32 PM. Contact: ###-####. t/s o/h n ok corrections made
|
Temporary Service | 4/2/2007 | 4/2/2007 | 4/2/2007 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/2/2007 at 9:29:49 AM. Contact: ###-####. called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 250.53(G) rod shall be flush with or below ground level, 110.12(C) there shall be no broken parts or foreign material in panel, 110.13(A) equipment shall be firmly secured
|