Final | 3/17/2008 | 3/18/2008 | 3/18/2008 | A | PASS |
Jack Frank
|
|
|
sean Phone #: ###-#### ok card signed
|
Final | 3/7/2008 | 3/10/2008 | 3/10/2008 | A | PART |
Bob Reichert
|
|
|
SHAWN NOTE: PARTIAL FINAL Phone #: ###-#### looked at east side up and down, talked about strapping, labels, open neutral in outlet, box covers, left correction notice NEC 110.26 shall provide work space about electrical equipment; all paragraphs, all electrical- see outside air handlers and mechanical rooms
|
Final | 3/6/2008 | 3/7/2008 | 3/7/2008 | P | PART |
Bob Reichert
|
|
|
sean - partial Phone #: ###-#### west 1/2 top and bottom looked at, need to fix clearances for disconnects in air handling areas add conduit supports in same areas, fix receptacle in elevator room, find listing for bleachers, will call for rest later
|
Electrical Rough-In | 1/30/2008 | 1/31/2008 | 1/31/2008 | A | PASS |
Bob Reichert
|
|
|
sean Phone #: ###-#### ok to cover ceilings anop
|
Electrical Rough-In | 1/30/2008 | 1/30/2008 | 1/30/2008 | P | CANC |
Bob Reichert
|
|
|
shawn Note above ceiling Phone #: ###-#### see conference
|
Conference | 1/30/2008 | 1/30/2008 | 1/30/2008 | P | DONE |
Bob Reichert
|
|
|
shawn Note above ceiling Phone #: ###-#### talked about strapping conduit exiting wall and fixture whips
|
Electrical Rough-In | 1/28/2008 | 1/29/2008 | 1/29/2008 | P | DONE |
Bob Reichert
|
|
|
ralph Phone #: ###-#### ok to cover hard lids east 1st floor and elevator room
|
Electrical Rough-In | 1/22/2008 | 1/23/2008 | 1/23/2008 | A | PART |
Bob Reichert
|
|
|
sean Phone #: ###-#### ok to cover hard lids anop, baths, storage rooms, elevator room
|
Electrical Rough-In | 1/17/2008 | 1/17/2008 | 1/18/2008 | P | PART |
Jack Frank
|
|
|
shawn Note: above ceiling Phone #: ###-#### ceilings anop
|
Permanent Service | 1/2/2008 | 1/3/2008 | 1/3/2008 | A | PASS |
Bob Reichert
|
|
|
John; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s u/g n ok, sticker on indoor main gear
|
Electrical Rough-In | 12/7/2007 | 12/10/2007 | 12/10/2007 | A | PASS |
Bob Reichert
|
|
|
john Phone #: ###-#### walls ok to cover anop
|
Electrical Rough-In | 12/4/2007 | 12/5/2007 | 12/5/2007 | A | PASS |
Mike Kinnear
|
|
|
Sean; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok cover walls only anop
|
Electrical Rough-In | 11/20/2007 | 11/21/2007 | 11/21/2007 | P | PASS |
Bob Reichert
|
|
|
sean Phone #: ###-#### walls only ok to cover anop, reviwed clearance for elevator disconnect
|
Electrical Rough-In | 11/16/2007 | 11/19/2007 | 11/19/2007 | A | PASS |
Bob Reichert
|
|
|
sean Phone #: ###-#### hard lids only anop ok to cover
|
Conference | 11/15/2007 | 11/15/2007 | 11/15/2007 | P | DONE |
Bob Reichert
|
|
|
shawn Phone #: ###-#### talked about disconnects, starters, strapping flex, clearances, fan coil installations
|
Electrical Rough-In | 11/14/2007 | 11/14/2007 | 11/14/2007 | P | PART |
Bob Reichert
|
|
|
shaun Phone #: ###-#### walls only anop ok to cover
|
Electrical Rough-In | 11/5/2007 | 11/5/2007 | 11/5/2007 | P | PART |
Bob Reichert
|
|
|
shaun Phone #: ###-####ok to cover west 2nd floor gym wall only,anop, signed plan for west wall from earlier inspection
|
Electrical Rough-In | 11/2/2007 | 11/5/2007 | 11/5/2007 | A | CANC |
Jack Frank
|
|
|
shawn Phone #: ###-#### met contr told him to get his permit attached to new BLD permit, they are working on a expired permit for another BLD contr
|
Electrical Rough-In | 10/18/2007 | 10/18/2007 | 10/18/2007 | P | PART |
Mike Kinnear
|
|
|
shawn Phone #: ###-#### ok cover east exterior wall in gym only
|
Electrical Rough-In | 9/26/2007 | 9/26/2007 | 9/26/2007 | P | PASS |
Bob Reichert
|
|
|
sean Phone #: ###-#### walls only, east side only anop ok to cover
|
Electrical Rough-In | 8/9/2007 | 8/10/2007 | 8/10/2007 | P | PASS |
Bob Reichert
|
|
|
shawn - underground Phone #: ###-#### ok to pour anop, 2nd floor, west
|
Electrical Rough-In | 7/10/2007 | 7/11/2007 | 7/11/2007 | P | PART |
William E Thomas
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang 1. as noted on prints ok.
|
Electrical Rough-In | 5/24/2007 | 5/25/2007 | 5/25/2007 | A | PASS |
Bob Reichert
|
|
|
mike Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles west side u/g ok to cover
|
Electrical Rough-In | 5/2/2007 | 5/3/2007 | 5/3/2007 | A | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover u/g east side anop
|
Electrical Rough-In | 4/2/2007 | 4/3/2007 | 4/3/2007 | A | PASS |
Bob Reichert
|
|
|
Contact is Perry. This is for an upgraded UFER ground for the existing service. Phone #: ###-#### ok to cover gec
|