Final | 5/17/2007 | 5/17/2007 | 5/17/2007 | P | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
Electrical Rough-In | 4/19/2007 | 4/19/2007 | 4/19/2007 | P | PASS |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok to pour equi-pot grid
|
Electrical Rough-In | 4/4/2007 | 4/4/2007 | 4/4/2007 | P | PART |
Bob Reichert
|
|
|
Mike swimming pool; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corrections made, ok to cover u/g from house to pool equip and pool light and cover
|
Electrical Rough-In | 4/3/2007 | 4/3/2007 | 4/3/2007 | P | FAIL |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall callede contr, left corr notice, nec 300.5 minimum burial depth shall be 18" for non-metallic raceways, 680.10 no u/g wiring shall be within 5' of pool edge, 352.26 there shall not be more than 360 degrees bend in rnc betwee pull points
|