Final | 12/10/2007 | 12/10/2007 | 12/10/2007 | P | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Justin Yount . 1. final ok. .
|
Final | 12/6/2007 | 12/6/2007 | 12/6/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Justin Yount met contractor, left correction notice, nec 210.52(C)(1) countertop receptacles shall be installed such that 24" spacing is maintained,210.8(A)(3) outdoor receptacles shall be gfci protected, BCC shall install switches for upstairs bath light and fan
|
Electrical Rough-In | 6/1/2007 | 6/1/2007 | 6/1/2007 | P | PASS |
Bob Reichert
|
|
|
for garage and trench cover. Phone #: ###-#### Internet Inspection Request from: Justin Yount corrections made, u/g house to garage ok to cover, garage ric ok
|
Rough-In Permanent Service | 5/17/2007 | 5/18/2007 | 5/18/2007 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Justin Yount ok cover ri house only. garage corrections not made 1 1/4 stapling also sub panel needs to have insolated neutral & gronding fixed p/s u/g n ok note no under ground between house & garage has been done.
|
Final | 5/15/2007 | 5/16/2007 | 5/16/2007 | A | CANC |
Bob Reichert
|
|
|
Between Raymond and Liberty on Poplar. Phone #: ###-#### Internet Inspection Request from: Justin Yount called contr, wrong type inspection told to check when scheduling
|
Rough-In Permanent Service | 5/16/2007 | 5/16/2007 | 5/16/2007 | A | FAIL |
Bob Reichert
|
|
|
Between Raymond and Liberty on Poplar. Phone #: ###-#### Internet Inspection Request from: Justin Yount called contr, left corr notice, 314.16 boxes shall have free space for conductors, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 230.2 only 1 service to building shall be installed, BCC all boxes and make-up shall be done, u/g shall be inspected before cover, service to be done at ri, gec connected in crawl space
|