Final | 5/22/2007 | 5/22/2007 | 5/22/2007 | P | FAIL |
William E Thomas
|
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles the pvc conduit for the data lines need to be secured and straped per the code
|
Electrical Rough-In | 4/13/2007 | 4/13/2007 | 4/13/2007 | P | PASS |
Bob Reichert
|
|
|
chad ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made, ric upstairs only ok
|
Electrical Rough-In | 4/12/2007 | 4/12/2007 | 4/12/2007 | P | FAIL |
Bob Reichert
|
|
|
chad-- ###-#### --call 1st before insp called, left corr notice, nec 300.4(A)&(D) edge of bored holes and mc cable shall be 1 1/4" from edge of framing members, 330.30(B) mc cable shall be secured within 12" of box, 110.12(A) unused openings shall be closed, 300.6(A) mc cable shall be protected from corrosion if on copper warer pipe
|