Rough-In Permanent Service | 5/14/2007 | 5/15/2007 | 5/15/2007 | A | PASS |
William E Thomas
|
|
|
Please re-inspect. Corrections have been made per inspector. Thanks Phone #: ###-#### x0000 Internet Inspection Request from: BRIAN KEITH ri ok, ps reconnect ok
|
Final | 4/20/2007 | 4/23/2007 | 4/23/2007 | A | FAIL |
Jack Frank
|
|
|
circuit for water heater in basement, upgrade service. Thank you. Kim Furhman should be home, ###-#### Phone #: ###-#### x0000 Internet Inspection Request from: BRIAN KEITH corr. fee due, called 250.104 shall bond around anything that isolates metal piping, 250.24 all grds and bonds shall be at main p/s not sub panels , isolate grds and neutrals at sub pnaels, remove spliced grd wire at subpanel, BCC no violations retained , wiring for hot tub shall meet NEC 680, connectors for all cables old subpanel garage, circuit directory be specific, 334.15 protect new wiring in basement, 300.4 nail plates and 11/4"
|