Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE07-01473
StatusFinaled
Name C H ELECTRIC
Site Address 6298 W CONTRACTOR ST
Project Name 
Customer Number 
ePlanReview 
Description
service & inside wiring // bld permit pulled prior to city annexing parcel // $10,000.00 initial value per cert ///final value is $24,000 per faxed document 11-16-07ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/19/20079/19/20079/19/2007PPASS
DetailsBob Reichert
c h Phone #: ###-#### ok to final, no card to sign
Final8/28/20078/29/20078/29/2007ANH
DetailsJack Frank
Chris; Phone #: ###-#### Internet Inspection Request from: Hattie James
card posted
Permanent Service8/21/20078/21/20078/21/2007PPASS
DetailsBob Reichert
chris Phone #: ###-#### p/s u/g n ok (3 meters)
Electrical Rough-In8/16/20078/16/20078/16/2007PPASS
DetailsBob Reichert
NOTE: UIFER Phone #: ###-#### ok to backfill gec
Electrical Rough-In8/3/20078/3/20078/3/2007PPART
DetailsJack Frank
chris - uffer Phone #: ###-#### ok for concrete cover
Electrical Rough-In4/30/20074/30/20074/30/2007PPASS
DetailsBob Reichert
chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ric ok
Electrical Rough-In4/27/20074/27/20074/27/2007PFAIL
DetailsBob Reichert
chris - re-inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr, corrections not all made
Rough-In Permanent Service4/25/20074/25/20074/25/2007PFAIL
DetailsBob Reichert
Chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, nec 250.86 metal boxes shall be grounded, 300.4(A)&(D) edge of bored holes, mc cable, and ent shall be 1 1/4" from edge of framing members, 330.30(B) mc cable shall be secured within 12" of box, 250.52(A)(3) shall utilize concrete encased electrode, 110.22 disconnects shall be identified and dufficient durability for conditions-inside and outside, BCC address shall be posted, job id sticker shall be posted, each meter requires permit, may need house panel