Final | 1/16/2008 | 1/16/2008 | 1/16/2008 | P | PASS |
Bob Reichert
|
|
|
ok to final
|
Permanent Service | 6/5/2007 | 6/6/2007 | 6/6/2007 | A | NH |
Jack Frank
|
|
|
spencer; Phone #: 8###-#### Internet Inspection Request from: Barbara Stitt notice posted called left message
|
Rough-In Permanent Service | 4/26/2007 | 4/27/2007 | 4/27/2007 | A | CANC |
Bob Reichert
|
|
|
Spencer; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see p/s for time and notes
|
Permanent Service | 4/27/2007 | 4/27/2007 | 4/27/2007 | A | FAIL |
Bob Reichert
|
|
|
Spencer; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met contr, told patio roof to close to service, will remove and recall, left corr notice, nec 230.24(A) service drop conductors shall be min 8' over roof
|