Final | 8/10/2007 | 8/13/2007 | 8/13/2007 | A | PASS |
Pat Lass
|
|
|
final on hot tub & pool Phone #: ###-#### Internet Inspection Request from: DJ Carman
|
Final | 8/9/2007 | 8/10/2007 | 8/10/2007 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman called still needs permit for hot tub
|
Final | 5/10/2007 | 5/10/2007 | 5/10/2007 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman needs outlet between 10ft and 20ft, also needs permit for hot tub and all wiring shall meet requirements of 680 called
|
Final | 5/8/2007 | 5/8/2007 | 5/8/2007 | A | NR |
Jack Frank
|
|
|
equipotential grounding grid Phone #: ###-#### Internet Inspection Request from: DJ Carman see added r/i
|
Electrical Rough-In | 5/8/2007 | 5/8/2007 | 5/8/2007 | A | PASS |
Jack Frank
|
|
|
equipotential grounding grid Phone #: ###-#### Internet Inspection Request from: DJ Carman ok
|
Electrical Rough-In | 5/2/2007 | 5/2/2007 | 5/2/2007 | P | PASS |
William E Thomas
|
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: DJ Carman ug ok
|
Electrical Rough-In | 5/1/2007 | 5/1/2007 | 5/1/2007 | P | FAIL |
Bob Reichert
|
|
|
trench inspection Phone #: ###-#### Internet Inspection Request from: DJ Carman met contr, called elect contractor, left corr notice, nec 680.10 min burial depth of pvc shall be 18" within 5' of pool, 300.5 min burial depth pvc shall be 18" except under slab shall be 12"
|
Electrical Rough-In | 4/27/2007 | 4/30/2007 | 4/30/2007 | A | PART |
Jack Frank
|
|
|
light wet niche Phone #: ###-#### Internet Inspection Request from: DJ Carman potting for pool light fixture ok
|