Final | 11/8/2007 | 11/8/2007 | 11/8/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/8/2007 at 9:04:31 AM. Contact: ###-####. corrections made, ok to final
|
Final | 10/22/2007 | 10/23/2007 | 10/23/2007 | A | FAIL |
Bob Reichert
|
|
|
jim Note: call in for entrance Phone #: ###-#### called, left corr notice, nec 210.11(C)(1) small appliance branch circuits shall be provided with 20a circuit, 110.22 furnace disconnect shall be clearly labelled for purpose and "off" "on", 422.12(A) a/c disconnect shall be selected based on the basis of nameplate rating
|
Rough-In Permanent Service | 4/30/2007 | 4/30/2007 | 4/30/2007 | P | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/30/2007 at 9:52:21 AM. Contact: ###-####. see ri, wrong type request
|
Electrical Rough-In | 4/30/2007 | 4/30/2007 | 4/30/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/30/2007 at 9:52:21 AM. Contact: ###-####. corr made, ric ok
|
Rough-In Permanent Service | 4/26/2007 | 4/27/2007 | 4/27/2007 | P | CANC |
Bob Reichert
|
|
|
john ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see p/s and ri
|
Electrical Rough-In | 4/27/2007 | 4/27/2007 | 4/27/2007 | P | FAIL |
Bob Reichert
|
|
|
john ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left message, left corr notice, nec 300.5 direct burial conductors shall be 18" deep, 210.52 (A) (2) shall install recpt in kitchen 2' wall, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 shall not staple nm cable on edge
|
Permanent Service | 4/27/2007 | 4/27/2007 | 4/27/2007 | P | PASS |
Bob Reichert
|
|
|
john ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s o/h n ok
|