ELE-Aging Inspection | 12/16/2009 | 12/16/2009 | 12/23/2009 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 12/23/2009 | 12/23/2009 | 12/23/2009 | A | PASS |
Jack Frank
|
|
|
no action
|
Electrical Rough-In | 10/16/2008 | 10/17/2008 | 10/17/2008 | A | PASS |
Jack Frank
|
|
|
Scheduled via mobile device. Phone #: 8663263 ok
|
Electrical Rough-In | 10/16/2008 | 10/16/2008 | 10/16/2008 | P | FAIL |
Jack Frank
|
|
|
joe- call 1st before insp Phone #: ###-#### met owner corr needs a device for slices, wires just twisted, free length ok conductors of 6", required outlet spacing, staple cables within 8" of boxes 15 amp overcurrent for #14 AWG use manufacture's breakers sq D nail plates and 11/4" where required SABC for outlets in new pantry ,or put refer on it's own outlet
|
Electrical Rough-In | 1/8/2008 | 1/9/2008 | 1/9/2008 | P | CANC |
Jack Frank
|
|
|
joe Phone #: ###-#### see added conference
|
Conference | 1/9/2008 | 1/9/2008 | 1/9/2008 | P | DONE |
Jack Frank
|
|
|
joe Phone #: ###-#### told owner NEC requirements and city requirements for r/i, and needs calcs for service
|