Final | 10/25/2007 | 10/25/2007 | 10/25/2007 | P | PASS |
Jack Frank
|
|
|
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
|
Rough-In Permanent Service | 5/14/2007 | 5/14/2007 | 5/14/2007 | P | PASS |
Jack Frank
|
|
|
Thank you Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i ok p/s u/g new ok
|
Rough-In Permanent Service | 5/11/2007 | 5/11/2007 | 5/11/2007 | P | FAIL |
Jack Frank
|
|
|
contact jeff ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corr called left message all 4 units, 314.3 no steel fittings in plastic boxes (range), 314.20 all outside boxes shall be flush, 314.17 staple 8" of boxes, 250.24 terminate GEC at neutral bus not equip grd bus, BCC complete all makeup and have attic accesses installed
|