Final | 6/12/2007 | 6/12/2007 | 6/12/2007 | P | PASS |
Bob Reichert
|
|
|
re-vised final Chris Sirani ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis correction made, ok to final, signed occ card
|
Final | 6/7/2007 | 6/7/2007 | 6/7/2007 | P | PART |
William E Thomas
|
|
|
final again thank you Chirs Sirani contact ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis 1. temp occcu approved 2. the low voltage cables and junction box above the buisness managers offices must be done according to the NEC.
|
Final | 6/6/2007 | 6/7/2007 | 6/7/2007 | A | FAIL |
William E Thomas
|
|
|
Chris Sirani contact final Thank-You Phone #: ###-#### Internet Inspection Request from: Debby Ellis 1. low voltage cables dangeling through the cieling 2. no cover plates on the receps and switches.
|
Electrical Rough-In | 5/21/2007 | 5/22/2007 | 5/22/2007 | A | PASS |
Jack Frank
|
|
|
chris - ceiling; Phone #: ###-#### Internet Inspection Request from: Delphine Kavanaugh ok
|
Conference | 5/8/2007 | 5/9/2007 | 5/9/2007 | A | DONE |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met elec contr and general, reviewed what needs done, left corr notice to owner nec 110.12(A) unused openings shall be closed, 330.30(A) mc cable shall be secured within 12" of box, 358.30(A) emt shall be secured within 3' of box, 725.3 abandoned cl 2 & 3 cable shall be removed, 300.11(A) cables and raceways shall not be supported on ceiling grid BCC no violations shall be retained
|
Electrical Rough-In | 5/7/2007 | 5/7/2007 | 5/7/2007 | P | PASS |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover new walls only
|
Electrical Rough-In | 5/4/2007 | 5/7/2007 | 5/7/2007 | A | FAIL |
Bob Reichert
|
|
|
chris ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice to owner and elect contr, BCC no violations shall be retained for electrical: obvious, but not all inclusive until opened up violations appear to be: open boxes in ceiling, mc cable and emt not strapped, abandoned wiring in ceiling, outlets above ceiling, wiring on grid, foreign piping systems over panels, work space about electrical equipment not sufficient, redundant grounding for patient care areas not provided, no access to parts of job, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members
|
Electrical Rough-In | 5/3/2007 | 5/4/2007 | 5/4/2007 | A | FAIL |
Bob Reichert
|
|
|
Chris Sirani contact ###-#### / Rough-In / Thank-You Phone #: ###-#### Internet Inspection Request from: Wendy Waters called contr, told elec permit not tied to bld, put stop work on job, fee due 2X
|