Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE07-01586
StatusFinaled
Name POWER PLUS INC
Site Address 1070 N CURTIS RD
Project NameCURTIS PROF PLAZA
Customer Number17355
ePlanReview 
Description
Electrical Permit - Alteration: misc. lighting power
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/12/20076/12/20076/12/2007PPASS
DetailsBob Reichert
re-vised final Chris Sirani ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis correction made, ok to final, signed occ card
Final6/7/20076/7/20076/7/2007PPART
DetailsWilliam E Thomas
final again thank you
Chirs Sirani contact ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis
1. temp occcu approved
2. the low voltage cables and junction box above the buisness managers offices must be done according to the NEC.
Final6/6/20076/7/20076/7/2007AFAIL
DetailsWilliam E Thomas
Chris Sirani contact final Thank-You Phone #: ###-#### Internet Inspection Request from: Debby Ellis
1. low voltage cables dangeling through the cieling
2. no cover plates on the receps and switches.
Electrical Rough-In5/21/20075/22/20075/22/2007APASS
DetailsJack Frank
chris - ceiling; Phone #: ###-#### Internet Inspection Request from: Delphine Kavanaugh ok
Conference5/8/20075/9/20075/9/2007ADONE
DetailsBob Reichert
chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met elec contr and general, reviewed what needs done, left corr notice to owner nec 110.12(A) unused openings shall be closed, 330.30(A) mc cable shall be secured within 12" of box, 358.30(A) emt shall be secured within 3' of box, 725.3 abandoned cl 2 & 3 cable shall be removed, 300.11(A) cables and raceways shall not be supported on ceiling grid BCC no violations shall be retained
Electrical Rough-In5/7/20075/7/20075/7/2007PPASS
DetailsBob Reichert
chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover new walls only
Electrical Rough-In5/4/20075/7/20075/7/2007AFAIL
DetailsBob Reichert
chris ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice to owner and elect contr, BCC no violations shall be retained for electrical: obvious, but not all inclusive until opened up violations appear to be: open boxes in ceiling, mc cable and emt not strapped, abandoned wiring in ceiling, outlets above ceiling, wiring on grid, foreign piping systems over panels, work space about electrical equipment not sufficient, redundant grounding for patient care areas not provided, no access to parts of job, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members
Electrical Rough-In5/3/20075/4/20075/4/2007AFAIL
DetailsBob Reichert
Chris Sirani contact ###-#### / Rough-In / Thank-You Phone #: ###-#### Internet Inspection Request from: Wendy Waters called contr, told elec permit not tied to bld, put stop work on job, fee due 2X