Final | 6/21/2007 | 6/21/2007 | 6/21/2007 | P | PASS |
William E Thomas
|
|
|
dino Phone #: ###-#### final ok, no card on site.
|
Final | 6/19/2007 | 6/19/2007 | 6/19/2007 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/19/2007 at 6:55:01 AM. Contact: ###-####. looked at x-ray and ok, called contr to do panel schedule and be sure occ card there, then call for final
|
Final | 6/6/2007 | 6/6/2007 | 6/6/2007 | A | PART |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 6/6/2007 at 6:56:17 AM. Contact: ###-####. T/O ok, need to see the x-ray machine only for the final
|
Final | 6/5/2007 | 6/5/2007 | 6/5/2007 | P | PART |
William E Thomas
|
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Patricia Smith cieling ok for cover, walls ok for final, T/O card needs to be signed. We still need to see the x-ray equipment for a final inspection an permanent occupancy.
|
Electrical Rough-In | 5/9/2007 | 5/10/2007 | 5/10/2007 | A | PART |
Jack Frank
|
|
|
deno; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
called needs bushings for low voltage conduits, install jumper where new plumbing valves installed dielectric union, note make sure #12 green installed in conduit for xray equipment
|
Conference | 5/8/2007 | 5/8/2007 | 5/8/2007 | A | DONE |
Bob Reichert
|
|
|
met contr, wrote corr notice to owner saidBCC no violations shall be retained, example: emt, pvs, mc shall be strapped per code, no openings in boxes, boxes shall be mounted, electrical panel not in bathroom, mc shall be hospital grade with redundand grounding in x-ray room, metal boxes shall be grounded, plans shall be complete, u/g shall be under slab, maintain 1 1/4" for holes and cable and pvc
|
Electrical Rough-In | 5/8/2007 | 5/8/2007 | 5/8/2007 | P | CANC |
Bob Reichert
|
|
|
dene - call for key location; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see conference
|