Final | 10/26/2007 | 10/26/2007 | 10/26/2007 | P | PASS |
William E Thomas
|
|
|
Grove Park lobby 1750 Grove. Call upon arrival Phone #: ###-#### Internet Inspection Request from: Sandee Johnson . 1. final ok--no signature card on sight. .
|
Electrical Rough-In | 8/16/2007 | 8/17/2007 | 8/17/2007 | A | PASS |
Jim Schmer
|
|
|
tim Note: front lobby only Phone #: ###-####
|
Electrical Rough-In | 8/15/2007 | 8/16/2007 | 8/16/2007 | A | FAIL |
Bob Reichert
|
|
|
ceiling grid; in lobby where new ceiling is; Tim; Phone #: ###-#### Internet Inspection Request from: Hattie James called, left corr notice, nec 110.12(A) unused openings in boxes shall be closed, 330.30(B) mc cable shall be secured within12" of box, 300.11(A) cables and raceways shall not be supported by grid, BCC low voltage cables shall not be supported bt grid
|
Electrical Rough-In | 7/26/2007 | 7/26/2007 | 7/26/2007 | P | PART |
Pat Lass
|
|
|
tim - wall; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang outside entry ok
|