Permanent Service | 5/17/2007 | 5/18/2007 | 5/18/2007 | A | FAIL |
Jack Frank
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Victoria Beall paitial corr only 110.26(F)(2) remove everything foreign to elect from below panel gas pipe ,etc. 240.24(A) panel set too high, 250.104(A)(1) bond water system, install 2 grd rods, needs conn for GEC, 408.4 specific panel schedule, address wiring to range and dryer? called owner note Idaho power hooked p/s up on the weekend with no inspection frist
|