Permit Information
Permit NumberELE07-01811
StatusFinaled
Name HEAVY DUTY ELECTRIC LLC
Site Address 1708 S SHOSHONE ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/24/20075/25/20075/25/2007APASS
DetailsBob Reichert
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, ok to final
Final5/21/20075/22/20075/22/2007AFAIL
DetailsWilliam E Thomas
justin; Phone #: ###-#### Internet Inspection Request from: Delphine Kavanaugh
guide wires to low and need to see the panel inside to verify what has been done in the closet
Final5/17/20075/18/20075/18/2007PCANC
DetailsBob Reichert
justin- ###-#### - call 1st before insp not done, see rip
Rough-In Permanent Service5/17/20075/18/20075/18/2007PPASS
DetailsBob Reichert
justin- ###-#### - call 1st before insp met contr left corr notice, told to call for Monday am inspection to correct following: nec 312.5 abrasion protection shall be provided for all conductors entering enclosures, 250.33 shall install 2 ground rods, 250.52(A) shall ground water pipe entering house, 110.3(A) shall use listed clamps, 230.24 shall provide 8' clearance over roof surface, 240.24(D)(E) shall not have overcurrent devices in closet,BCC shall install 2" mast, NOTE: this may not be final correction bnotice, reserve right to disconnect power if corrections not made. p/s o/h rec ok