Final | 5/24/2007 | 5/25/2007 | 5/25/2007 | A | PASS |
Bob Reichert
|
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, ok to final
|
Final | 5/21/2007 | 5/22/2007 | 5/22/2007 | A | FAIL |
William E Thomas
|
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Delphine Kavanaugh guide wires to low and need to see the panel inside to verify what has been done in the closet
|
Final | 5/17/2007 | 5/18/2007 | 5/18/2007 | P | CANC |
Bob Reichert
|
|
|
justin- ###-#### - call 1st before insp not done, see rip
|
Rough-In Permanent Service | 5/17/2007 | 5/18/2007 | 5/18/2007 | P | PASS |
Bob Reichert
|
|
|
justin- ###-#### - call 1st before insp met contr left corr notice, told to call for Monday am inspection to correct following: nec 312.5 abrasion protection shall be provided for all conductors entering enclosures, 250.33 shall install 2 ground rods, 250.52(A) shall ground water pipe entering house, 110.3(A) shall use listed clamps, 230.24 shall provide 8' clearance over roof surface, 240.24(D)(E) shall not have overcurrent devices in closet,BCC shall install 2" mast, NOTE: this may not be final correction bnotice, reserve right to disconnect power if corrections not made. p/s o/h rec ok
|