Final | 6/6/2007 | 6/7/2007 | 6/7/2007 | A | PASS |
William E Thomas
|
|
|
Please call so I can meet you over there. Thanks, Dick Phone #: ###-#### Internet Inspection Request from: Richard Jones final ok
|
Rough-In Permanent Service | 6/7/2007 | 6/7/2007 | 6/7/2007 | P | PASS |
William E Thomas
|
|
|
Please call so I can meet you over there. Thanks, Dick Phone #: ###-#### Internet Inspection Request from: Richard Jones p/s o/h reconnect ok
|
Permanent Service | 5/31/2007 | 5/31/2007 | 5/31/2007 | A | FAIL |
William E Thomas
|
|
|
Please do as early as possible. Thanks, Richard Jones Phone #: ###-#### Internet Inspection Request from: Richard Jones 1. 314.41 Covers for the J-Boxes shall be of the same type material as the boxes themselves. 2. 344.30 Mast shall be secured within three feet of the top 3. 250.52A1 ground the water pipe within 5' of entrance to the building. 4. 250.53A ground rod shall be in full contact with the earth 5. 240.24D overcurrent devices shall not be located in a closet 6. 314.17B all cables entering into boxes shall be secured to the boxes B.C.C. "No violation shall be retained" KO seals and clamps shall be instaled on the boxes where theyare not being used.
|