Final | 9/7/2007 | 9/10/2007 | 9/10/2007 | A | PASS |
Mike Kinnear
|
|
|
shawn Phone #: ###-#### ok final corrections made
|
Final | 9/6/2007 | 9/6/2007 | 9/6/2007 | P | FAIL |
Mike Kinnear
|
|
|
sean Phone #: ###-#### gfci within 25ft from air cond., disconnect at furnace, & disconnect for garage t/w sean
|
Electrical Rough-In | 8/9/2007 | 8/9/2007 | 8/9/2007 | P | PASS |
Mike Kinnear
|
|
|
r/i on detached garage//Shawn ###-#### ok cover ri
|
Electrical Rough-In | 7/6/2007 | 7/6/2007 | 7/6/2007 | P | PASS |
Mike Kinnear
|
|
|
chris - concrete patch on groundrod Phone #: ###-#### ok cover concrete patch ok cover under ground conduit
|
Permanent Service | 7/6/2007 | 7/6/2007 | 7/6/2007 | P | PASS |
Mike Kinnear
|
|
|
chris - concrete patch on groundrod Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 6/13/2007 | 6/13/2007 | 6/13/2007 | P | PART |
Mike Kinnear
|
|
|
shawn - uffer only - as soon as possible ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok cover grounding electrode conductor with concrete or sealer we need to reinspect after it is covered
|
Conference | 6/12/2007 | 6/12/2007 | 6/12/2007 | P | PASS |
Mike Kinnear
|
|
|
Shawn - Mike this is for a uffer ground; Phone #: ###-#### Internet Inspection Request from: Darla Downs conf they can connect grounding electrode to exessing rebar in the foundation or they can clean the tar off footing foundation & pour 2inch or more concrete over it
|
Electrical Rough-In | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | PASS |
Pat Lass
|
|
|
shawn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith R/I Ok will add required receps. service has no concrete encased electrode
|