Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE07-02064
StatusFinaled
Name NORTHWEST ELECTRICAL
Site Address 7701 NORTHVIEW
Project Name 
Customer Number23388
ePlanReview 
Description
Electrical Permit - New: New Electrical Service, Site Lighting, branch power, lighting, etc.-ele08-01261 created for the service for the pump station with a value of $6,000///see scanned and attached documents
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/25/20086/25/20086/25/2008PPASS
DetailsJack Frank
jared Phone #: ###-#### ok card signed
Permanent Service6/20/20086/23/20086/23/2008ACANC
DetailsJack Frank
Jason Phone #: ###-#### called needs new permit for new p/s
Final5/28/20085/28/20085/28/2008PPART
DetailsJack Frank
jared Phone #: ###-#### t/o ok card signed still needs kitchen equipment
Final4/22/20084/22/20084/22/2008PPART
DetailsJack Frank
jared - area A Phone #: ###-#### ok anop no t/o too much outside lighting for sffits not ready
Final3/24/20083/25/20083/25/2008APART
DetailsJack Frank
Scheduled by a contractor via Hello! on 3/24/2008 at 9:13:29 PM. Contact: ###-####. areas B & C,mech mezzanine ok for t/o anop
Electrical Rough-In2/27/20082/28/20082/28/2008APASS
DetailsWilliam E Thomas
jared Phone #: ###-####
. .1. as noted on prints hard lid ok to cover. .
Electrical Rough-In2/21/20082/22/20082/22/2008APART
DetailsJack Frank
Jared-ceiling cover please Phone #: ###-#### ceilings anop
Electrical Rough-In2/13/20082/13/20082/13/2008PPART
DetailsMike Kinnear
jared Phone #: ###-#### ok cover ceilings & walls anop
Permanent Service1/31/20082/1/20082/1/2008APASS
DetailsPat Lass
jared Phone #: ###-####
check transformer grounding and bonding later 12 1/2 % rule and landing GEC on neutral also 1/2 in flex is only good for 20 a and should not be used to incase GEC
P/S U/G N Ok
Electrical Rough-In1/25/20081/25/20081/25/2008PPART
DetailsMike Kinnear
gerad- ceiling insp Phone #: ###-#### ok cover ceilings & walls anop
Electrical Rough-In12/19/200712/20/200712/20/2007APART
DetailsJack Frank
jared Phone #: ###-#### hard ceilings and 1 wall anop
Electrical Rough-In12/3/200712/4/200712/4/2007APASS
DetailsJack Frank
jared Phone #: ###-#### walls and u/g anop
Electrical Rough-In11/30/200711/30/200711/30/2007PPASS
DetailsMike Kinnear
jerod - Note: underground - from bld to first light pole Phone #: ###-#### ok cover under ground conduit
Electrical Rough-In11/29/200711/30/200711/30/2007APASS
DetailsBob Reichert
jerod Note: underground Phone #: ###-#### ok to cover u/g anop
Electrical Rough-In11/27/200711/28/200711/28/2007PPART
DetailsJack Frank
gerald Note: lightpole bases Phone #: ###-#### ok
Electrical Rough-In11/26/200711/26/200711/26/2007PPART
DetailsMike Kinnear
Jared Phone #: ###-#### ok cover walls only anop
Conference9/25/20079/26/20079/26/2007ADONE
DetailsJack Frank
jared Phone #: ok
Temporary Service7/10/20077/10/20077/10/2007PCANC
DetailsJack Frank
jared Phone #: ###-#### see added r/i also contr needs permit for t/s shall not use job permit for t/s
Electrical Rough-In7/10/20077/10/20077/10/2007PPART
DetailsJack Frank
jared Phone #: ###-#### u/g and floor boxes anop
Electrical Rough-In7/9/20077/9/20077/9/2007PPART
DetailsJack Frank
jerod Note: underground Phone #: ###-####
u/g for parking lot lignts anop
Electrical Rough-In7/3/20077/3/20077/3/2007PPART
DetailsJack Frank
jared; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
u/g area A anop
Electrical Rough-In6/29/20076/29/20076/29/2007PPART
DetailsJack Frank
jared - underground; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang partial u/g anop
Electrical Rough-In6/19/20076/19/20076/19/2007PCANC
DetailsJack Frank
jared - underground; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called u/g for phone service conduit we do not inspect that, only the inside blding conduit
Electrical Rough-In6/18/20076/18/20076/18/2007PPART
DetailsJack Frank
Ufer ground inspection. Please call Jared Moyle at ###-#### with any questions. Phone #: ###-#### Internet Inspection Request from: Jeff Durham ok
Electrical Rough-In6/12/20076/12/20076/12/2007PPART
DetailsJack Frank
Contact is Jared. Please inspect underground electrical. Phone #: ###-#### Internet Inspection Request from: David Bonner 4" 70ft run inside N end u/g also S end phone and power to old blds, inside and outside 1st section of u/g from bld to jbox in field
Electrical Rough-In6/8/20076/8/20076/8/2007PPART
DetailsJack Frank
Underground / Underslab Inspection. Please call Jared Moyle at ###-#### for additional information. Phone #: ###-#### Internet Inspection Request from: Jeff Durham u/g ok service lateral